Allegion Fire, life safety and accessibility codes 15 − A legible sign must be permanently mounted on the exit door to indicate that the locking device will release 15 seconds after the application of force to the door opening hardware, tactile sign also required Note: While the concept of tactile signage for life safety was introduced earlier, the specific requirement for tactile/Braille instructions on delayed egress doors was solidified in the 2020 edition and carries forward into 2025 Operating hardware for the doors in this section shall be installed between 900–1100 mm above the finished floor (previously 1200 mm maximum) Security for banks and mercantile floor areas ( 2025, 2020, 2015, 2010: 3.4.6.17; 2005: 3.4.6.16) Requirements of this section may be waived for bank and mercantile occupancies due to security concerns Buildings must be sprinklered throughout Consult section for specific requirements Emergency cross over access to floor areas ( 2025, 2020, 2015, 2010: 3.4.6.18; 2005: 3.4.6.17) In a building more than six stories high: − Doors providing access to floor areas from exit stairs shall not have locking devices to prevent access to the floor area from which the travel distance up or down to an unlocked door is more than two stories − Doors that provide access to the floor area (as required above) shall have signage on the stair side to indicate that they are openable from the stair side − A master key for all locked doors in a stairwell shall be provided in a designated location accessible to fire-fighters, or the locked door shall have a wire glass panel not less than 0.0645 m2 in area and located not more than 300 mm from the door opening hardware − If access to floor areas through unlocked doors is required by this section, an occupant entering the floor area must have access, through unlocked doors within the floor area, to at least one other exit Barrier-free doorways and doors ( 2025, 2020, 2015: 3.8.3.6; 2010, 2005: 3.8.3.3) Every doorway in a barrier-free path of travel shall have a clear width of at least 850 mm (previously 800 mm) when the door is in the open position (measured from the face of the door at 90 degrees to the outside edge of the frame stop, the projection of exit devices are taken into account - appendix) If a swinging door in a barrier-free path is not equipped with a power operator, the latch side clearance must extend: − at least 600 mm beyond the door opening edge if the door swings toward the approach side, or − at least 300 mm beyond the door opening edge if the door swings away from the approach side The doorway of at least one bathroom within a residential suite must have a clear width of at least 800 mm when the door is in the open position Door operating devices shall be operable with one hand in a closed fist position, without requiring tight grasping, pinching with fingers, or twisting of the wrist, and unless otherwise stated, shall be operable with a force of not more than 22 N Thresholds shall be a maximum of 13 mm above the floor surface and shall be beveled Doors that provide a barrier-free path of travel at an entrance referred to in Article 3.8.2.7 shall be equipped with a power operator in a hotel, a building of group B, division 2 major occupancy, and a building of group A, B-division 3, D, or E major occupancy more than 500 m2 in building area − Controls for power operators shall be located in a barrier-free path of travel and consist of two separate activation devices, one centered between 150–300 mm above the floor, and the second centered between 900–1100 mm above the floor − Exception: Individual suite having an area less than 500 m2 in a building having only suites of assembly, care, business and personal services or mercantile occupancy if the suite is completely separated from the remainder of the building so that there is no access to the remainder of the building Door closers used in a barrier-free path of travel shall require a maximum force applied at the handle, push plate, or latch releasing device of no more than 38 N to operate an exterior door and 22 N to operate an interior door − Exception: Entrance to a dwelling unit, or where greater forces are required to close the door against prevailing difference in air pressure Door closers used on interior doors in a barrier-free path of travel shall have a closing period of not less than 3 seconds from the open position of 70 degrees to a point 75 mm from the closed position, measured from the leading edge of the latch side of the door − Exception: Dwelling unit entrance doors, delayed action not required (appendix) Only the active leaf in a multiple leaf door in a barrier free path of travel needs to conform to the requirements In facilities other than those occupied by people with cognitive disabilities (ex. dementia), doors and frames in doorways used by the public that lead from a public corridor or that provide access to a public area shall have readily apparent visual contrast with adjacent wall surfaces