Allegion Fire, life safety and accessibility codes 9 General ( 2024, 2021, 2018, 2015: 1010.1; 2012 and prior: 1008.1) Section applies to means of egress doors and additional doors provided for egress purposes Must be readily distinguishable from surrounding finishes and easily recognizable as doors No mirrors or reflective materials on egress doors No curtains or decorations concealing egress doors Size of doors ( 2024, 2021, 2018, 2015: 1010.1.1; 2012 and prior: 1008.1.1) Minimum clear width 32 inches (813 mm) and sufficient for occupant load Measured between the face of the door and the stop on the frame, with door open 90 degrees At least one leaf of pairs of doors must provide 32 inches (813 mm) clear width Prior to the 2021 edition, the maximum width of a swinging door was limited to 48 inches (1219 mm) Egress doors in I-2 occupancies used for movement of beds: minimum of 41-1/2 inches (1054 mm) clear Minimum height: 80 inches (2032 mm), or 78 inches (1980 mm) to projecting hardware (see below) Projections into clear opening ( 2024, 2021, 2018, 2015: 1010.1.1.1; 2012 and prior: 1008.1.1.1) No projections into required clear width lower than 34 inches (864 mm) above the floor or ground Projections into clear opening width between 34–80 inches (864–2032 mm): 4 inches max (102 mm) Minimum 78- inch opening height measured to door closers, overhead door stops, power door operators, and electromagnetic locks − Note: Prior to the 2021 edition, the 78-inch height allowance was measured to door closers and stops Egress door types and direction of swing ( 2024, 2021, 2018, 2015: 1010.1.2; 2012 and prior: 1008.1.2) Typically, egress doors must be swinging doors hung on pivots or hinges—consult code for exceptions Manually operated horizontal sliding doors may be used for rooms with an occupant load of 10 people or less, in use groups other than group H Doors must swing in the direction of egress when serving a room with an occupant load of 50 or more or a group H occupancy (any load) Forces to unlatch and open doors ( 2024, 2021, 2018, 2015: 1010.1.3; 2012, 2009: 1008.1.3; 2006, 2003: 1008.1.2) New in 2021 edition operable force for hardware: − Hardware operated by pushing/pulling motion, 15 lbs (67 N) maximum to unlatch the door − Hardware operated by rotational motion, 28 inch-lbs (35 N-cm) maximum to unlatch the door Door opening force (forces applied at latch side of door): − Interior manually operated swinging egress doors other than fire doors: maximum opening force 5 lbs (22 N) − Other swinging, sliding, and folding doors, and doors required to be fire rated: door set in motion with 30 lbs (133 N) force, maximum, and door swings to a full-open position with 15 lbs (67 N) force, maximum Thresholds ( 2024, 2021: 1010.1.6; 2018, 2015: 1010.1.7; 2012, 2009: 1008.1.7; 2006, 2003: 1008.1.6) 1/2 inch (13 mm) maximum height for doors other than sliding doors in dwelling units 3/4 inch (19 mm) maximum height for sliding doors in dwelling units Changes in height of 1/4 inch (6 mm) or less may be vertical; changes over 1/4 inch (6 mm) must be beveled with a slope of 1:2 maximum Door operations ( 2024, 2021: 1010.2; 2018, 2015: 1010.1.9; 2012, 2009: 1008.1.9; 2006, 2003: 1008.1.8) Unless otherwise allowed within this section, egress doors must always be openable from the egress side without using a key, special knowledge or effort Highlights of the I-Codes: International Building Code® 1 (IBC) and International Fire Code (IFC) 1 2024, 2021, 2018, 2015, 2012, 2009, 2006, and 2003 editions The use groups for the I-Codes include the following (consult the code for complete descriptions): A - Assembly B - Business E - Educational F - Factory industrial H - High-hazard I - Institutional M - Mercantile R - Residential S - Storage U - Utility and misc. Note: In this code reference guide, “fire protection system” means an approved sprinkler system, approved fire alarm system or both. Numbers in brackets ( ) refer to applicable sections of the code publication.