30 Allegion Fire, life safety and accessibility codes Decoded: Door closers may either release upon fire alarm or may contain an integral smoke detector. For some retrofit applica- tions, a battery-operated holder with an integral smoke detector may be used in conjunction with a separate mechanical closer. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, a closing device must be installed on every fire door. A couple of exceptions to that requirement are communicating doors between hotel rooms and the inactive leaf of pairs leading to rooms not normally occupied by humans, like a mechan- ical room (where acceptable to the AHJ). Closers must be securely attached with steel screws or through-bolts, and the closer must be adjusted so the door latches each time it closes. NFPA 80 divides the operation of fire doors into three categories (2022: 6.1.4; 2019, 2016, 2013: 6.1.3; 2010, 2007: 6.1.4): 1) Self-closing door: the door is equipped with a closing device, and closes each time it is opened (no hold-open). 2) Automatic-closing door: the door closes and latches automatically when released by an automatic fire detector. 3) Power-operated fire door: the automatic operator is automatically disconnected during an alarm condi- tion, allowing the door to close and latch. Life safety The International Building Code (IBC) and NFPA 101 contain similar requirements for holding open fire doors, although they are more specific with regard to locations where automatic-closing doors are allowed, and how they are released. Automatic-closing doors must have the capability of manual release, and be automatically released by smoke detectors meeting the requirements of NFPA 72. NFPA 101 states that when automatic-clos- ing doors are used on stairs, they must be wired so all doors close when one door closes due to smoke detec- tion, protecting the exit enclosure. (NFPA 101: 7.2.1.8; IBC 2024, 2021, 2018: 716.2.6; 2015, 2012: 716.5.9; 2009: 715.4.8) The following codes and standards were researched for this article. For more information, determine the code that is being enforced and refer to the appropriate edition of that code. ADA Standards for Accessible Design: 2010 ICC/ANSI A117.1: Accessible and Usable Buildings and Facilities - 2009, 2017 NFPA 80: 2007, 2010, 2013, 2016, 2019, 2022 NFPA 101: 2006, 2009, 2012, 2015, 2018, 2021, 2024 International Building Code (IBC): 2009, 2012, 2015, 2018, 2021, 2024 For more information, please visit www.nfpa.org.