14 Allegion Fire, life safety and accessibility codes Doors and door hardware (3.3.1.13) A door that opens into or is located within a public corridor and provides access to an exit shall provide a clear opening of 850 mm (previously 800 mm) minimum for a single door or active leaf of a pair (1050 mm minimum for doors required to accommodate moving patients in beds per 3.3.3.4) Exit access doors shall be readily openable in the direction of exit travel, requiring no keys, special devices, or specialized knowledge (exception for contained use area or impeded egress zone) Exit access doors shall be operable with one hand and one releasing operation (exception for dwelling unit/suite) Dwelling unit doors may have on additional releasing operation, with no keys, special devices or knowledge Door release hardware must be installed between 900–1100 mm above the finished floor (previously 1200 mm maximum) Except for hotels and motels, doors opening onto a public exit access corridor must not relock automatically (3.3.4.5) Door swing - exits ( 2025, 2020, 2015, 2010: 3.4.6.12; 2005: 3.4.6.11) Except where sliding doors are permitted (2015, 2010: 3.4.6.14; 2005: 3.4.6.13), every exit door shall open in the direction of exit travel and swing on a vertical axis Self-closing devices - exits ( 2025, 2020, 2015, 2010: 3.4.6.13; 2005: 3.4.6.12) Exit doors normally required to be kept closed shall be self-closing and shall not be secured in the open position except as allowed by section 3.1.8.12(1) Door release hardware ( 2025, 2020, 2015, 2010: 3.4.6.16; 2005: 3.4.6.15) Locking, latching, and other fastening devices on the principal entrance door and all exit doors shall permit the door to be readily opened from the egress side with one operation and without the use of keys, special devices, or specialized knowledge (exceptions for contained use area, impeded egress zone, electromagnetic locks and security doors on banks and mercantile facilities) If the door is equipped with a latch, a device which will release the latch and allow the door to swing wide open when a force of not more than 90 N is applied in the direction of travel to the exit shall be installed on: − Every exit door from a floor area of an assembly occupancy with an occupant load of more than 100, − Every door leading to an exit lobby from an exit stair shaft and every exterior door leading from an exit stair shaft in a building having an occupant load of more than 100, − Every exit door from a floor area containing a high hazard industrial occupancy Except where required by section 3.8.3.6 (Barrier-Free Doorways and Doors), every exit door shall open with a force of not more than 90 N after the latch is released, force applied at the releasing device Electromagnetic locks without latches, pins, or other devices to keep the door closed may be installed on exit doors except doors leading directly from high hazard industrial occupancies, provided: − Building is equipped with a fire alarm system, and − Locking device and all similar devices in the exit access leading to the exit unlock upon fire alarm, and − Locking device releases upon loss of power to the lock and associated auxiliary controls, and − Device releases upon operation of a manually operated switch accessible only to authorized personnel, and a force of 90 N applied to the door opening hardware initiates an irreversible process that releases the locking device within 15 seconds and device shall not relock until the door has been opened, and − Upon release, the locking device must be manually reset by the switch referred to above, and − If more than one locking device of this type is used in a building, the switch must release and reset all locking devices simultaneously (appendix), and Highlights of the National Building Code of Canada1 Note: In this code reference guide, “fire protection system” means an approved sprinkler system, approved fire alarm system, or both. Numbers in brackets ( ) refer to applicable sections of the code publication. 1 2025, 2020, 2015, 2010 and 2005 editions Use Groups (consult code for complete descriptions): A - Assembly B - Care, Treatment, or Detention C - Residential D - Business and Personal Service E - Mercantile F - Industrial (divided into Divisions 1, 2, and 3 to indicate level of hazard)