18 Allegion Fire, life safety and accessibility codes Elevator lobby exit access door locking ( 2024, 2021: 7.2.1.6.4; 2018, 2015, 2012, 2009: 7.2.1.6.3) Except for newly-constructed high-rise buildings, doors that separate the elevator lobby from the exit access are permitted to be locked electronically, if the following criteria are met: − This type of locking must be allowed by the occupancy chapter. In recent editions of NFPA 101, it is allowed in new and existing assembly, educational, day-care, health care, ambulatory health care, hotels and dormitories, apartment buildings, mercantile, business, industrial, and storage occupancies − Lock is listed per UL 294 or UL 1034 (2024 ed) − Building is protected throughout with a fire alarm and sprinkler system and movement of water through the system actuates the fire alarm system − Elevator lobby is protected by an approved smoke detection system that, upon detection of smoke, activates the fire alarm system − Activation of fire alarm by means other than manual pull stations unlocks the elevator lobby door(s) − Loss of power to the elevator lobby locking system unlocks the assembly—once unlocked, the door(s) will not relock until the fire alarm has been manually reset − Where elevator lobby doors remain latched after unlocking, latch-releasing hardware is mounted on the door and has an obvious method of operation − A two-way communication system allows communication between the elevator lobby and a constantly staffed control point − Control point staff is trained and capable of providing emergency assistance − Doors are not required to comply with requirements pertaining to delayed egress locks or access controlled egress doors Panic hardware and fire exit hardware (7.2.1.7) Actuating portion of panic hardware must measure at least half the width of the door leaf Device must be mounted between 34–48 inches (865–1220 mm) above finished floor (30–48 inches (762–1220 mm) for existing applications) Door locations requiring panic hardware are listed within the individual occupancy chapters: means of egress doors in assembly, day-care, and educational occupancies with an occupant load of 100 or more shall be permitted to have a latch or lock only if it is panic hardware Doors serving high hazard contents areas with occupant load of more than five shall be permitted to have a latch or lock, only if it is panic hardware Required panic hardware (except as allowed for detention and correctional occupancies), shall not be equipped with any locking device, set screw or other arrangement that prevents the release of the latch when pressure is applied to the releasing device No additional locking device (padlock, hasp, chain, deadbolt, etc.) shall be installed on a door which is required to have panic hardware Fire exit hardware may not be equipped with devices to hold the latch retracted, unless the devices are listed and approved for such purposes (i.e. electric latch retraction) Self-closing devices (7.2.1.8) Doors designed to normally be kept closed in a means of egress shall be self-closing doors and shall not be secured in the open position Exception: Doors can be automatic closing, if: − Upon release of the hold-open mechanism, the door becomes self-closing − Door can be easily released manually − Releasing mechanism is activated by approved smoke detectors installed per NFPA 72®, National Fire Alarm and Signaling Code, 2019 edition − Upon loss of power to the hold-open device the door becomes self-closing − Release of one door in a stair enclosure results in closing of all doors in that stairway Doors that are required to be self-closing and are not required to be automatic closing may have delayed action door closers − Note: A standard door closer without a hold-open mechanism is self-closing. A door with a closer and an electric or battery-operated hold-open mechanism actuated by smoke detectors is automatic-closing. Inspection of door openings ( 2024, 2021: 7.2.1.14; 2018, 2015, 2012, 2009: 7.2.1.15) In new and existing assembly, educational, day-care, hotels and dormitories, apartment buildings, mercantile, business, industrial, storage, and residential board and care occupancies, the following doors must be inspected and tested annually: − Doors with panic hardware or fire exit hardware − Door assemblies in exit enclosures − Electrically controlled egress doors − Door assemblies with special locking arrangements (delayed egress, sensor release egress doors and elevator lobby doors) Written record of inspections and testing must be signed and retained for review by AHJ Functional testing must be performed by individuals with knowledge and understanding of the type of door being tested Copyright © 2023 NFPA Highlights of NFPA 101®, Life Safety Code®
Fire Life Safety and Accessibility Codes Book
| Title Name |
Pages |
Delete |
Url |
| Empty |
Ai generated response may be inaccurate.
Search Text Block
Page #page_num
#doc_title
Hi $receivername|$receiveremail,
$sendername|$senderemail wrote these comments for you:
$message
$sendername|$senderemail would like for you to view the following digital edition.
Please click on the page below to be directed to the digital edition:
$thumbnail$pagenum
$link$pagenum
Your form submission was a success.
Downloading PDF
Generating your PDF, please wait...
This process might take longer please wait