Allegion Fire, life safety and accessibility codes 27 Panic hardware is defined by the International Building Code (IBC) as “a door-latching assembly incorporating a device that releases the latch upon the application of a force in the direction of egress travel.” Panic hardware can be classified as either a touchpad or pushpad type device, a crossbar device or recessed panic hardware. Where panic hardware is required by code based on occupancy type and occupant load: International Building Code (editions from 2006–present): Each door in a means of egress equipped with a latch or lock, serving assembly or educational occupancies with an occupant load of 50 people or more. High hazard occupancies (any occupant load). International Building Code (2003): Each door in a means of egress that is equipped with a latch or lock, serving assembly or educational occupancies with an occupant load of 100 people or more. High hazard (H-1, H-2, H-3, or H-5) occupancies (any occupant load). NFPA 101 (2003–present): Required means of egress doors equipped with latches or locks serving assembly, educational or day-care occupancies with an occupant load of 100 people or more. High hazard contents areas with an occupant load in excess of five. Panic hardware is only required by code if both crite- ria are met; the occupancy type must be one of those listed above and the occupant load must be more than 50 people or 100 people depending on the code refer- enced. Although NFPA 101 is the only code discussed in this article that has a separate classification for day- care occupancies, the IBC also considers children’s day-care facilities of a certain size as educational occu- pancies. Therefore, the requirement for panic hardware would apply if the day-care facility had the referenced occupant load. In some cases, panic hardware may not be required on the main exit door serving certain occupancies, on egress doors serving exterior spaces, or on stadium gates. Consult the applicable code for these exceptions. Beginning with the 2002 edition, NFPA 70®, National Electrical Code® required certain rooms housing electrical equipment to have doors that open in the direction of egress and were “equipped with panic bars, pressure plates or other devices that are normally latched but open under simple pressure.” Technically, a hospital latch or paddle-type release would have met this requirement, but the fact that the words “panic bar” were used in the code prompted many code officials to require panic hardware. (The intent was clarified in the 2014 edition.) The 2008 edition of NFPA 70 added language which requires these outswinging doors with devices that open under simple pressure when the door is within 25 feet of the required working space. Unlike other means of egress where panic hardware is required on all doors in the egress route to the public way, electrical rooms only require panic hardware on doors within 25 feet of the required working space. The 2014 edition of NFPA 70 further clarifies the require- ment by mandating “listed panic hardware” on these rooms, rather than devices that open under simple pres- sure. This mandates panic hardware that is listed to UL 305 - Standard for Panic Hardware. For fire doors, fire exit hardware that is also listed to UL 10C is required. The types of electrical rooms that require panic hard- ware vary, based on which edition of NFPA 70 has been adopted. According to the 2020 and 2023 editions, personnel doors serving the following types of rooms, within 25 feet of the working space, must comply: Rooms housing equipment of 1000 volts, nominal, or less, with equipment rated 800 amps or more that contains overcurrent devices, switching devices, or control devices Electrical vaults and rooms housing equipment of more than 1000 volts, nominal Transformer vaults, battery rooms, and modular data centers In the 2023 edition, a change was made to specify that personnel doors serving these rooms must open at least 90 degrees The IBC also refers to panic hardware for electrical rooms, and this requirement was modified in the 2021 edition to be more closely aligned with the requirements of NFPA 70. However, because the National Electrical Code’s requirements for panic hardware vary from one Decoded: Panic hardware Panic hardware, also known as an exit device (or fire exit hardware when used on fire doors), is designed to provide fast and easy egress to allow building occupants to exit safely in an emergency.