Allegion Fire, life safety and accessibility codes 11 − On a pair of doors in a group B, F, or S occupancy, where the inactive leaf has no surface trim such as knobs, levers, panic bars, or similar hardware, manual flush bolts may be allowed if: A) the door serves an occupant load of less than 50 occupants, or B) the building has an approved fire sprinkler system and the inactive leaf is not required for egress width − On a pair of doors serving patient rooms in group I-2 occupancy when the inactive leaf is not required for egress width: self-latching bolts are acceptable (not manual flush bolts) − Refer to fire door latching requirements Stairway doors ( 2024: 1010.2.6; 2021: 1010.2.7; 2018: 1010.1.9.12; 2015: 1010.1.9.11; 2012: 1008.1.9.11; 2009: 1008.1.9.10; 2006, 2003: 1008.1.8.7) Interior stairway means of egress doors shall be openable from both sides without the use of a key or special knowledge or effort Exceptions: − Stairway discharge doors may be locked on the access side - openable from egress side − Doors may be locked on the stair side if they can be unlocked simultaneously without unlatching upon all of the following: a signal from the fire command center or from a single location inside the building’s main entrance, a fire alarm signal, failure of the power supply to the lock (changed in 2024) − In high-rise buildings (over 75 feet (23 m) in height), where electrified locks are installed, a telephone or other two-way communication device is required at every fifth floor − Consult code for exceptions related to facilities with single exit stairs Locking arrangements in educational occupancies ( 2024: 1010.2.7; 2021: 1010.2.8; 2018: 1010.1.4.4) Egress doors from classrooms, offices, and other occupiable rooms in group E, group B educational, and group I-4 may be locked to prevent access Doors must be able to be unlocked from the outside with a key or other approved means Doors must allow free egress per Section 1010.1.9 Panic hardware, fire door hardware, and door closers must not be modified Fire door modifications must comply with NFPA 80 Remote operation of locks is also permitted Panic and fire exit hardware ( 2024: 1010.2.8; 2021: 1010.2.9; 2018, 2015: 1010.1.10; 2012, 2009: 1008.1.10; 2006, 2003: 1008.1.9) Panic hardware is required for doors equipped with locks or latches which serve rooms or spaces with an occupant load of 50 or more in groups A or E, and in group H occupancies of any occupant load Exceptions: − Entrances described in section on locks and latches − Doors serving group A or E occupancies may have electrified locking hardware released in by a sensor or by a switch in the door-mounted hardware Actuating portion of device must extend at least half the width of the door leaf Max. force to unlatch is 15 lbs (67 N): refer to accessibility standards for more restrictive requirements Balanced doors with panic hardware must have pushpad type panics and the pad shall not extend more than one-half the width of the door measured from the latch side Panic hardware must be listed per UL 305 Panic hardware used on fire doors is fire exit hardware and must be listed per UL 305 and UL 10C New in 2021: Panic hardware required for refrigeration machinery rooms over 1000 square feet (93 m2) Electrical rooms with equipment rated 800 amperes or more, and over 6 feet wide, that have overcurrent devices, switching devices or control devices: exit access doors within 25 feet of the required working space must be equipped with panic hardware − Also applies to transformer vaults, battery/energy storage rooms, and modular data centers − Refer to NFPA 70 for additional requirements Monitored or recorded egress, and access control ( 2024: 1010.2.9; 2021: 1010.2.10; 2018: 1010.1.9.3) Egress doors may be electrically monitored or recorded and access control systems may be used to limit access Door must allow free egress without a key or special knowledge or effort—if not, the system must comply with one of the special locking arrangements sections